The electronic industry clean room is a dust-free environment designed specifically for the production of electronic components. By controlling parameters such as particles, microorganisms, temperature and humidity, and static electricity, it ensures the stability of precision manufacturing processes. Botai editor will take you to learn about relevant knowledge.
1、 Fire resistance requirements
The clean room of the electronic industry is designed according to the second level fire resistance rating.
2、 Main structure
The main structure is suitable for large spaces and large-span column grids, and it is not advisable to use internal wall load-bearing systems.
3、 Decorative materials
The decoration materials of electronic industry cleanrooms shall not use materials that release substances that have an impact on electronic products.
4、 Multi layer construction
Large electronic industry clean rooms often adopt a "sandwich" multi-layer structure with upper and lower technical interlayers.
5、 Lighting fixtures
For high-end cleanrooms, in order to minimize the impact on the unidirectional and parallel airflow, it is advisable to use so-called teardrop shaped lighting fixtures.
6、 The plane is determined by the process
The process layout of clean rooms in the electronic industry should adapt to the flexibility of electronic product development, meet the needs of product production process transformation and expansion of production.
7、 Large scale process equipment
The installation and maintenance requirements of large-scale production process equipment should be considered, and necessary transportation channels and installation or maintenance ports that do not affect the clean production environment should be set up.
8、 Anti static requirements
Electronic industry cleanrooms often set up anti-static environments according to production process requirements to suppress the generation of static electricity and quickly and safely eliminate the generated static electricity.
9、 Special gases
The storage and distribution room for special gases should be separated from the clean room by fire-resistant walls, with a fire resistance limit of no less than one hour. The storage area for toxic silane or its mixture gas cylinders should be open on at least three sides.
10、 Air shower room
The shower room should be adjacent to the clean work clothes changing room, and a single shower room should be designed for thirty people per room. If the number of personnel exceeds five, a bypass door should be set up. If the number of people is large or the passage time is shortened, a tunnel style shower room can be set up.