1 Overview
With the development of industry, many electrical and factory equipment use direct currentSystem power supply, the positive and negative poles of the DC system are not grounded. For ungrounded(IT)The distribution system should be monitored for insulation resistance to ensure the safety of the power supply systemFully operational.
AIM-D100-CAThe series of DC insulation monitoring instruments can be applied in0~1000VIn the DC system, it is used for online monitoring of the positive direction of the DC ungrounded systemNegative pole to ground insulation resistance. When the insulation resistance is lower than the set value, a warning will be issuedOr an alarm signal.The product is mainly aimed atDC 0~1000VDesigned for insulation monitoring of electric vehicle charging devices, it can also be applied to energy storage DC and substationsThe DC screen of the stationUPSDC systems such as power supply systems, photovoltaic DC systems, and other DC power grids.
2Functional Features
Resistance monitoring function. The product can monitor the insulation resistance of the positive and negative poles of the DC system to ground. When the insulation resistance is lower than the set warning and alarm values,Capable of issuing warnings and alarm signals.
Voltage monitoring function. The product can monitor the voltage between the positive and negative poles of the DC system, as well as the voltage between the positive and negative poles and the ground. The measurement range is0~1000V
■ Current monitoring function. The product can monitor the DC system current, onlyAIM-D100-CAIThe model has this function.
■LEDIndication function. The product panel has functions of operation, communication, and malfunctionLEDIndicator lights can display the status of the product.
■ Communication networking function. The product features1 roadRS485Interface, usingModbus-RTUProtocol allows for data exchange.
■ Metal casing. The product adopts a metal shell, wall mounted installation, and can also be installed using accessory rails.
■ Plug and unplug terminals. The product adopts plug-in terminal wiring, which is convenient for wiring and installation.
3technical indicators

5 External dimensions