Phone
13695838022
-
Address
Longgen Industrial Zone, Liushi Town, Yueqing City, Wenzhou City, Zhejiang Province
Zhejiang Zhidian Instrument Co., Ltd
13695838022
Longgen Industrial Zone, Liushi Town, Yueqing City, Wenzhou City, Zhejiang Province
1、 Scope of application
DZ47LE-63 series residual current circuit breakerAssembled from DZ47 high breaking miniature circuit breaker and residual current release. This product is suitable for AC 50Hz, rated working voltage 230V~400V, and rated current up to 100A in power lines. It mainly consists of zero sequence current transformers, electronic component boards, residual current circuit breakers, and has overload and short circuit protection functions. It can also be added with overvoltage and undervoltage protection functions according to user needs to provide indirect contact protection for people, as well as overcurrent protection for buildings and similar power lines. It can also provide protection against fires caused by grounding faults that persist due to the malfunction of overcurrent protection devices. Leakage circuit breakers with overvoltage protection can also provide protection against high voltage caused by power grid faults.2、 Model and specifications

3、 Structural features
The DZ47LE-63 residual current circuit breaker is assembled and integrated from residual current release accessories and DZ47 circuit breaker, thus maintaining the same time current action characteristics as DZ47. Its mechanical assembly can be completed by enterprises in the factory or on site. The leakage release characteristic parameters are set by the factory and cannot be adjusted by the user. The leakage release cannot be disassembled to avoid affecting performance. The residual current release has two levels of shell current: 32A and 50A, which can be connected to 10mm ² and 25mm ² wires respectively.4、 Normal working conditions and installation conditions
The ambient air temperature ranges from -5 degrees Celsius to 40 degrees Celsius, with an average of no more than 35 degrees Celsius within 24 hours.5、 Main parameters and technical performance
Main specifications:| Rated voltage Ue (V) | number of poles | Shell level rated current lnm (A) | Rated current (A) | Rated leakage current (mA) | Rated leakage non operating current (mA) | Rated leakage breaking time (s) | Overvoltage protection setting value (V) | Rated short-circuit breaking capacity lcn (A) |
| 230 | 1+N | 32 | 6. 10, 16, 20, 25, 32 | 30 ; fifty | 15 ; twenty-five | ≤0.1 | 280±5% | 6000 |
| 2 | ||||||||
| 400 | 3 | |||||||
| 3+N | ||||||||
| 4 | ||||||||
| 230 | 1+N | 50 | 6. 10, 16, 20, 25, 32, 40, 50, 63 | 30 ; fifty | 15 ; twenty-five | 4500 | ||
| 2 | ||||||||
| 400 | 3 | |||||||
| 3+N | ||||||||
| 4 |
| test current | rated voltage | Set time | Expected results | Initial state | notes |
| 1.13ln | all values | t≥1h | Do not release | cold state | The current steadily rises to the specified value within 5 seconds |
| 1.45ln | all values | t<1h | trip | Hot state | |
| 2.55ln | all values | 1<t<60s | trip | cold state | Close the auxiliary switch and turn on the power supply |
| 5ln | all values | t≥0.1s | Do not release | cold state | Close the auxiliary switch and turn on the power supply |
| 10ln | all values | t<0.1s | trip | cold state | Close the auxiliary switch and turn on the power supply |
| Temperature ℃ | -15 | -5 | 0 | 10 | 20 | 30 | 40 | 55 |
| Rated current correction factor | 1.19 | 1.15 | 1.13 | 1.06 | 1.05 | 1 | 0.96 | 0.89 |
| Rated current ln (A) | Nominal cross-sectional area of copper wire (mm ²) |
| 10 and below | 1.5 |
| 10~20 | 2.5 |
| 20~25 | 4 |
| 25~32 | 6 |
| 32~50 | 10 |
| 50~63 | 16 |
6、 Appearance and installation dimensions
DZ47LE-63
DZ47LE-50 Large Shell Series