E-mail
sales@txele.com
- Phone
-
Address
No. 2550, Waibiaosong Road, Jiading District, Shanghai
Shanghai Taixi Electric Co., Ltd
sales@txele.com
No. 2550, Waibiaosong Road, Jiading District, Shanghai
1、 Scope of application
TXU3(ALU3 Surge Protector)-B. C and D series large flow modularizationALU3Surge protectors are suitable for TT, IT, TN-S, TN-C, TN-C-S and other power supply systems with AC 50/60Hz and rated voltage of 380V or below, to protect the power grid from lightning strikes or surge overvoltage. Its design basis complies with C61643-1 and GB18802-2002. It can discharge 100KA lightning current, and the shell is designed to be installed on a 35mm electrical guide rail. The disconnection device can automatically disconnect it from the power grid, and the status indicator window changes from green to red.2、 Model and specifications

3、 The function of surge protectors
ALU3Surge protective deviceA varistor with excellent nonlinear characteristics is used, and under normal circumstances, the surge protector is in an extremely high resistance state, with almost zero leakage current, ensuring the normal power supply of the power system. When the power system experiences overvoltage as described above, the surge protector immediately conducts rapidly within nanoseconds, limiting the amplitude of the overvoltage to the safe operating range of the equipment. Simultaneously release the energy of the overvoltage. Subsequently, the surge protector quickly changed to a high resistance state, thus not affecting the normal power supply of the power system.4、 Structure and working principle
ALU3Surge protective deviceIn a three-phase four wire system, three phase wires and one neutral wire are all connected to the grounding wire with a protector. Under normal circumstances, the protector is in a high resistance state. When the power grid experiences surge overvoltage due to lightning strikes or other reasons, the protector will immediately conduct rapidly in nanoseconds, introducing the surge overvoltage into the ground and protecting the electrical equipment on the power grid. When the surge voltage passes through the protector and disappears, the protector returns to a high resistance state, so as not to affect the normal operation of the power grid.5、 Product Features
★ Adopting high-performance zinc oxide varistors with independent intellectual property rights6、 Main technical parameters
| model | TXU3-B30 | TXU3-B40 | TXU3-B60 | |||
| Maximum continuous operating voltage Uc (V~) | 320 | 385 | 320 | 385 | 320 | 385 |
| Protection level Up (kV) | <2.0 | <2.0 | <2.0 | <2.5 | <2.5 | <3.0 |
| Nominal discharge current ln (8/20 μ s) (kA) | 30 | 40 | 60 | |||
| Maximum discharge current Imax (8/20 μ s) (kA) | 60 | 80 | 100 | |||
| Response time t (ns) | <25 | |||||
| Fuse or circuit breaker (A) | 63 | |||||
| Working environment (℃) | -40℃~+85℃ | |||||
| Relative humidity (%) | ≤95%(25℃) | |||||
| Connecting wire cross-sectional area (mm ²) | ≥25 | ≥35 | ≥35 | |||
| Grounding wire cross-sectional area (mm ²) | ≥35 | ≥35 | ≥35 | |||
| model | TXU3-C15 | TXU3-C20 | ||||||||
| Maximum continuous operating voltage Uc (V~) | 275 | 320 | 375 | 420 | 440 | 275 | 320 | 375 | 420 | 440 |
| Protection level Up (kV) | <1.2 | <1.5 | <1.8 | <2.0 | <2.0 | <1.2 | <1.5 | <1.8 | <2.0 | <2.0 |
| Nominal discharge current ln (8/20 μ s) (kA) | 15 | 20 | ||||||||
| Maximum discharge current Imax (8/20 μ s) (kA) | 30 | 40 | ||||||||
| Response time t (ns) | <25 | |||||||||
| Fuse or circuit breaker (A) | 25 | 32 | ||||||||
| Working environment (℃) | -40℃~+85℃ | |||||||||
| Relative humidity (%) | ≤95%(25℃) | |||||||||
| Connecting wire cross-sectional area (mm ²) | ≥16 | ≥25 | ||||||||
| Grounding wire cross-sectional area (mm ²) | ≥16 | ≥25 | ||||||||
| Alarm line cross-sectional area (mm ²) | ≥1.5 | |||||||||
| model | TXU3-D5 | TXU3-D10 | ||||||
| Maximum continuous operating voltage Uc (V~) | 275 | 320 | 385 | 420 | 275 | 320 | 385 | 420 |
| Protection level Up (kV) | <1.2 | <1.5 | <1.8 | <2.0 | <1.2 | <1.5 | <1.8 | <2.0 |
| Nominal discharge current ln (8/20 μ s) (kA) | 5 | 10 | ||||||
| Maximum discharge current Imax (8/20 μ s) (kA) | 10 | 20 | ||||||
| Response time t (ns) | <25 | |||||||
| Fuse or circuit breaker (A) | 10 | 16 | ||||||
| Working environment (℃) | -40℃~+85℃ | |||||||
| Relative humidity (%) | ≤95%(25℃) | |||||||
| Connecting wire cross-sectional area (mm ²) | ≥10 | ≥16 | ||||||
| Grounding wire cross-sectional area (mm ²) | ≥16 | ≥25 | ||||||
| Alarm line cross-sectional area (mm ²) | ≥1.5 | |||||||
7、 Installation location and application
8、 Appearance and installation dimensions
9、 Why use surge protectors
The destructive power of lightning is extremely strong, and external lightning protection (such as lightning rods) is not enough for switch mode power supplies. Lightning waves can directly or indirectly (through electromagnetic induction) invade various electrical and metal channels (such as power lines, signal lines, feeder lines, and metal pipelines). The lightning overvoltage and surge voltage generated from this will cause great harm to electronic, electrical equipment, and information network systems, ranging from damaging power lines to damaging equipment, causing system paralysis and incalculable losses.
10、 Ordering Notice
When placing an order, please indicate the following points:
Product model and name: such asALU3-CSurge protective device
Specification: such as Class C.
Maximum discharge current: 40kA.
Polar number: 2P
Order quantity: such as 730 pieces.