1、 Scope of application
C65 Circuit Breaker AccessoriesMN undervoltage release, MV overvoltage release, MN+MV overvoltage release, SD alarm contact, OF auxiliary contact are auxiliary functional components designed specifically for C65 circuit breakers. By providing overvoltage, undervoltage, and overvoltage detection to the power supply, they control the on/off of the circuit breaker, disconnect the distribution system circuit, or detect the circuit breaker signal. Can be used in conjunction with C65N, NB1 and other series circuit breakers.2、 Model meaning and main technical parameters
| product name | model | Rated working voltage Un | drop away voltage | Purpose: |
| Overvoltage release device | MV | 230V | Overvoltage value Uvo=270V ± 5% | When the power supply voltage rises between 270V ± 5%, the circuit breaker trips to achieve overvoltage protection of the line. |
| undervoltage release | MN | 230V | Undervoltage value Uoe=170V ± 5% | When the power supply voltage drops between 170V ± 5%, the circuit breaker trips to achieve under voltage protection of the line. |
| Overvoltage and undervoltage release device | MV+MN | 230V | Overvoltage value Uvo=270V ± 5% Undervoltage value Uoe=170V ± 5% |
When the rated power supply voltage of 220V rises to 270 ± 5% or drops to 170V ± 5%, the circuit breaker will trip to achieve line protection. |
| Alarm contact | SD | 115/230/400V | 1、3A | When the circuit breaker is disconnected due to a fault in the protected circuit, provide an alarm signal |
| auxiliary contact | OF | 115/230/400V | 1、3A | Provide auxiliary signals and control auxiliary circuits |
| Attachment Name | Rated insulation voltage Ui | Rated control power supply voltage Us | Release power consumption (W or VA) | pull-in voltage | |
| MX+OF shunt release+auxiliary contact | 415V | AC/DC: 220~380V; 110~220V | 240 | (0.7~1.1)Us | |
| AC/DC:24~48V | 120 | ||||
| MX+OF shunt release+auxiliary contact | active | 415V | AC/DC: 220~380V; 110~220V | 240 | (0.7~1.1)Us |
| AC/DC:24~48V | 120 | ||||
| passive | 415V | AC/DC: 220~380V; 110~220V | 240 | (0.7~1.1)Us | |
| AC/DC:24~48V | 120 | ||||
| MX shunt release | 415V | AC/DC: 220~380V; 110~220V | 240 | (0.7~1.1)Us | |
| AC/DC:24~48V | 120 | ||||
| Attachment Name | Rated current (A) | Number of contacts per group | ||
| AC:380V | AC:220V | DC:110V | ||
| Auxiliary contact OF | 3 | 6 | 1 | One normally open; A normally closed |
| Alarm contact SD | 3 | 6 | 1 | One normally open; A normally closed |
3、 Appearance and installation dimensions
4、 Ordering Notice
When placing an order, please indicate the following points: