Welcome Customer !

Membership

Help

Shanghai Taixi Electric Co., Ltd
Custom manufacturer

Main Products:

pharmamach>Products

Shanghai Taixi Electric Co., Ltd

  • E-mail

    sales@txele.com

  • Phone

  • Address

    No. 2550, Waibiaosong Road, Jiading District, Shanghai

Contact Now

CJT1 AC contactor

NegotiableUpdate on 05/20
Model
Nature of the Manufacturer
Producers
Product Category
Place of Origin

Overview

Scope of application: CJT1 series AC contactors (hereinafter referred to as contactors) are mainly used in power lines with AC 50Hz or 60Hz, rated working voltage up to 380V, and current up to 150A for long-distance connection and disconnection of circuits. They can be combined with appropriate thermal relays or electronic protection devices to form motor starters to protect circuits that may experience overload. The CJT1 AC contactor meets the standards of GB14048.4, IEC60947-4-1, and JB/T8730, and is an alternative product to the CJ10 series contactor. Model meaning

Product Details

Product Introduction

Scope of Application

The CJT1 series AC contactor (hereinafter referred to as the contactor) is mainly used in power lines with AC 50Hz or 60Hz, rated working voltage up to 380V, and current up to 150A for remote connection and disconnection of circuits. It can be combined with appropriate thermal relays or electronic protection devices to form a motor starter to protect circuits that may experience overload.
The CJT1 AC contactor meets the standards of GB14048.4, IEC60947-4-1, and JB/T8730, and is an alternative product to the CJ10 series contactor.

Model meaning

Some common models include:

CJT1-10,CJT1-20,CJT1-40,CJT1-60,CJT1-80,CJT1-100,CJT1-150

Normal working conditions and installation conditions

The ambient air temperature ranges from -5 ℃ to+40 ℃, with an average value not exceeding+35 ℃ within 24 hours.
Altitude: not exceeding 2000m.
Atmospheric conditions: When the maximum temperature is+40 ℃, the relative humidity of the air does not exceed 50%; Higher relative humidity can be allowed at lower temperatures, such as reaching 90% at+20 ℃. Special measures should be taken for occasional condensation caused by temperature changes.
Pollution level: Level 3.
Installation category: Class III.
Installation conditions: The inclination angle between the installation surface and the vertical surface shall not exceed ± 5 °.
Shock and vibration: The product should be installed and used in a place without significant shaking, shock, and vibration.

Main parameters and technical performance

Contactors are classified according to current levels: 10A, 20A, 40A, 60A, 100A, 150A.

The rated control power supply voltage Us for the coil is AC (50Hz): 36V, 110V, 127V, 220V, 380V.

Action condition: The suction voltage is (85%~110%) Us; The release voltage is (20%~75%) Us.

Main parameters and technical performance (see table).

model

rated voltage
(V)

rated current
(A)

Operating frequency
Times/h

Connection capability

breaking capacity

Electrical life
Ten thousand times

mechanical life
Ten thousand times

Control electric power
(KW)

Attraction coil

AC-3 AC-4

220V

380V

rated voltage
(V)

Starting power

Absorption power

CJT1-10

380

10

600

15Ue cosφ
=0.35±0.05
12le

15Ue cosφ=
0.35±0.05
10le

60

2

300

2.2

4

36,127,220,380

65

9

CJT1-20

380

20

600

60 2

5.5

10

36,127,220,380

140

9.5

CJT1-40

380

40

600

60 2

11

20

36,127,220,380

230

19

CJT1-60

380

60

600

60 1

17

30

36,127,220,380

485

95

CJT1-100

380

100

600

60 1

30

50

36,127,220,380

760

105

CJT1-150

380

150

600

60 0.6

43

75

36,127,220,380

950

110


structural characteristics

The structure and installation dimensions of this contactor are the same as those of CJ10. The arc extinguishing cover is composed of an arc resistant plastic arc cover and an iron grid plate, CJT1-60、 The base of 100 and 150 is made of reinforced plastic.
The CJT1-10-40A contactor adopts a double break direct acting structure, the 60-150A contactor contact system adopts a double break direct acting structure, and the electromagnetic system adopts a lever rotating structure. The contacts are made of new copper based silver free alloy materials. It has strong oxidation resistance, low and stable contact resistance, and good resistance to welding and wear, saving precious metals and reducing costs. The 20-40A contactor adopts U-shaped arc extinguishing plates and phenolic plastic arc extinguishing covers, while the 60-150A contactor adopts a new type of longitudinal and transverse grid staggered arrangement, and the DMC anti surge plastic arc extinguishing cover has good arc extinguishing performance.

Appearance and installation dimensions






model Overall dimensions
(AxBxC)
installation dimensions
(DxE)
n-φ F
CJT1-10 70x70x96.5 56x58 3-φ5 15
CJT1-20 92x102x110 76x68 3-φ5 15
CJT1-40 115x128x125 100x75 3-φ5.5 30
CJT1-60 170x178x135 98x160 3-φ7 30
CJT1-100 195x204x135 110x180 3-φ9 75
CJT1-150 222x232x154 130x205 3-φ11 75