Welcome Customer !

Membership

Help

Beijing Dingsheng Ronghe Technology Co., Ltd
Custom manufacturer

Main Products:

pharmamach>Products

DS/ET-PSA human static discharge alarm/human static discharge alarm comes with a 5-year warranty

NegotiableUpdate on 03/15
Model
Nature of the Manufacturer
Producers
Product Category
Place of Origin

Overview

DS/ET-PSA human static discharge alarm is an instrument suitable for human static discharge in flammable, explosive, and anti-static places. Its characteristic lies in the design of a reasonable human body static discharge resistor, which effectively controls the human body static discharge, prolongs the human body static discharge time, reduces the instantaneous human body static discharge energy, and enables the safe discharge of human body static electricity. At the same time, it can detect whether the contact between the human body and the static touch ball is reliable, and sound and light alarms indicate whether the static elimination is completed.

Product Details

PSA/PS-ADS/ET-PSA human electrostatic discharge alarm/human electrostatic discharge alarm 5-year warranty detailed information:

Electrical parameters of DS/ET-PSA human static discharge alarm

1. Working power supply: High performance built-in lithium battery
2. Sleep current: < 1mA
3. Working current: < 5mA
4. Working temperature:- 40℃~60℃
5. Response time:< 1s
6. Grounding resistance: ≤ 55 Ω
7. Explosion proof grade: ExiaIICT4 Gb
8. Withstand static voltage: ± 20KV
9. Alarm method: Sound and light alarm (>90dB, 30cm straight-line distance measurement)

DS/ET-PSA human static discharge alarm electromechanical reference number

1. Pole material: 304 stainless steel
2. Pole diameter: Φ38mm
3. Wall thickness of pole: 1.0mm
4. Product height: 1m
5. Touch ball diameter: Φ90mm
6. Installation flange wall thickness: 3.0mm
7. Grounding cable length: 3m straight PU cable

DS/ET-PSA Human Static Discharge Alarm Product Features

1. Ultra low power consumption design, no need to replace the battery during normal use
2. Touch sensitive sensing, no mechanical moving parts
3. Whole epoxy resin sealing, anti-corrosion, waterproof, moisture-proof
4. Explosion proof touch ball, safe release of static electricity, no electric shock sensation when in contact with the human body
5. Sound and light alarm indicates that the contact between the human body and the explosion-proof touch ball is reliable and static electricity has been discharged
6. The grounding wire is independently tested, and the grounding resistance meets the standard to ensure reliable grounding

DS/ET-PSA Human Static Discharge Alarm Reference Standard

The design of ET-PSA human static discharge alarm refers to the following national standards:
GB12158-2006 "General Guidelines for Preventing Static Electricity Accidents"
Article 14.3.13 stipulates that due to the widespread use of artificial fabric clothing, artificial fabrics are prone to static electricity, which often accumulates in people

On the body. To prevent sparks that may be generated by static electricity, it is necessary to inspect the operating platforms that enter the light oil pump room, the top of the light oil tank, and the light oil operation area

Install devices to eliminate human static electricity on escalators or at entrances in explosive hazardous areas. This static elimination device refers to a device made of metal tubes

The handrail should be touched by the human body to eliminate static electricity before entering these places.
SH3097-2000 "Design Specification for Static Electricity Grounding in Petrochemical Industry"
The ET-PSA human static discharge alarm has been certified by the National Center for Quality Supervision and Inspection of Explosion proof Electrical Products (NCEX) and meets the following standards:
GB3836.1-2010 Explosive Atmosphere Part 1: General Requirements for Equipment
GB3836.4-2010 Explosive Atmosphere Part 4: Equipment Protected by Intrinsic Safety Type "i"

DS/ET-PSA human static discharge alarm usage method

Quality Service Commitment:1.The warranty period is 18 months, with lifetime free maintenance.2.During the warranty period, except for human factors, we will repair or replace any defects or malfunctions caused by improper instrument design, materials, or processes free of charge3.Upon receiving notification from the user that the provided instrument has malfunctioned, respond within ten minutes.4.Ensure timely provision of necessary spare parts and consumables to users at the most favorable prices