The NHR-7300/7300R series LCD PID regulator/recorder is suitable for high-precision measurement and control systems, and can digitally display and adjust measurement signals such as temperature, pressure, liquid level, and speed; Can choose internal and external given (or valve position) control methods, which can replace amplifiers to directly drive actuators; Programmable control mode can be selected, and 61 target curves can be set to monitor, control, record, and remotely transmit the controlled object.
According to the control method, it can be divided into the following categories:
| NHR-7310/7310R Single channel self-tuning PID regulator/regulating recorder |
During automatic control, the input measurement value is compared with the internal target value and a control signal is output after calculation. |
| NHR-7320/7320R External PID regulator/regulation recorder |
During automatic control, the input measurement value is compared and calculated with the externally given input target value to output a control signal. |
| NHR-7330/7330R Valve position feedback PID regulator/regulating recorder |
During automatic control, control is divided into two modes based on the different types of control outputs Mode 1: Select analog control output: Compare the input measurement value with the internal target value and output the control signal. Mode 2: Select switch control output: When the percentage of control output is less than the valve position feedback value, the instrument output reverses. When the percentage of control output is greater than the valve position feedback value, the instrument output reverses. |
| NHR-7340/7340R Program PID regulator/regulation recorder |
According to the requirements of the production process, setting a target curve for control can achieve the operation of running, stepping, pausing, ending, and waiting states for curve control. |
instrument panel
|
|
|
| 160 * 80mm (Type A) | 80 * 160mm (Type B) | 96 * 96mm (Type C) |
|
① Display panel ② USB and SD interfaces ③ Confirm button ![]() Display channel switch key ![]() Time scale switch, manual/automatic switch key ![]() ④ Right cursor shift key ⑤ Left cursor shift key ⑥ Cursor up key ⑦ Cursor down key |
|
Simple visual indication
|
Wiring diagramNHR-7310 (R)/7340 (R) series instrument wiring diagram

NHR-7320 (R) series instrument wiring diagram

NHR-7330 (R) series instrument wiring diagram

|
Note 1: If different functions are marked on the same group of terminals in the wiring diagram, only one function can be selected. If RS485 and RS232 are connected to the same set of terminals, only one can be selected. Note 2: The direction of the wiring terminals on the back cover of the horizontal and vertical instruments is different, as shown in schematic diagram 1 |
|
instrument selectionNHR-73 □-□-□-□-□-□| ① Control method (Note 1) | ② Specification and size | ||
| code | control mode | code | Width * Height * Depth |
|
10 |
Single channel PID control External given control Valve position feedback control Program segment control |
A B C |
160 * 80 * 110mm (horizontal) 80 * 160 * 110mm (vertical) 96 * 96 * 110mm (Method) |
| ③ Control output (Note 1) | ④ Alarm output (Note 2) | ||
| code | Output type (load resistance RL) | code | Alarm channel (relay contact output) |
|
0 1 2 3 4 5 K1 K3 K4 K5 K6 K7 K8 K9 |
4-20mA(RL≤600Ω) 1-5V(RL≥250KΩ) 0-10mA(RL≤1.2KΩ) 0-5V(RL≥250KΩ) 0-20mA(RL≤600Ω) 0-10V(RL≥4KΩ) RELAY CONTACT OUTPUT Zero crossing trigger pulse output of thyristor Solid state relay driving voltage output Phase shifted trigger output Three phase thyristor zero crossing trigger pulse output Relay forward and reverse output Controllable silicon forward and reverse output (suitable for high-power loads) Solid state relay forward and reverse output |
X 1 2 3 4 5 |
no-output 1-limit alarm 2-limit alarm 3-limit alarm 4-limit alarm 5-limit alarm |
| ⑤ Power supply | |||
| code | Voltage range | ||
| A D |
AC/DC 100~240V(AC/50-60Hz) DC 20~29V |
||
| ⑥ Additional functions (all of the following functions can be selected, separated by "/", functions that are not selected can be omitted) | |||
| Transmission output (Note 2) | Communication output | ||
| code | Output channel | code | Communication interface (communication protocol) |
|
1 2 3 |
1-channel transmission output 2-channel transmission output 3-channel transmission output |
D1 D2 D3 |
RS-485 communication interface (Modbus RTU) RS232 communication interface (Modbus RTU) RS232C printing interface |
| Feed output | |||
| code | Feed output (output voltage) | ||
| 1P 2P |
1-channel feeding output 2-channel feeding output |
||
| Suitable for instruments with records | |||
| USB transfer function | Extended functionality | ||
| code | Transfer function | code | Extended functionality |
| U | USB card transfer (with 1GB USB flash drive) | SD | SD card expansion (capacity 8GB) |
| signal type | Range of measurement | signal type | Range of measurement |
| B S K E T J R N F2 Wre3-25 Wre5-26 Cu50 Cu53 Cu100 Pt100 BA1 |
400~1800℃ -50~1600℃ -100~1300℃ -100~1000℃ -100.0~400.0℃ -100~1200℃ -50~1600℃ -100~1300℃ 700~2000℃ 0~2300℃ 0~2300℃ -50.0~150.0℃ -50.0~150.0℃ -50.0~150.0℃ -200.0~650.0℃ -200.0~600.0℃ |
BA2 0~400Ω 0~350Ω 30~350Ω 0~20mV 0~100mV 0~20mA 0~10mA 4~20mA 0~5V 1~5V 0~10V 0-10mA square root 4-20mA square meter 0-5V square root 1-5V square root |
-200.0~600.0℃ -9999~99999 Special customization Special customization -9999~99999 -9999~99999 -9999~99999 -9999~99999 -9999~99999 -9999~99999 -9999~99999 Special customization -9999~99999 -9999~99999 -9999~99999 -9999~99999 |
| signal type | 4-20mA | 1-5V | 0-10mA | 0-5V | 0-20mA | 0-10V (specially customized) |
| Load resistance RL | RL≤480Ω | RL≥250KΩ | RL≤960Ω | RL≥250KΩ | RL≤480Ω | RL≥4KΩ |