E-mail
2945155087@qq.com
-
Phone
18953188556
-
Address
Xinsha Industrial Park
Jinan Zhongnuo Instrument Co., Ltd
2945155087@qq.com
18953188556
Xinsha Industrial Park
Zhongnuo GB/T 20284 Single Unit Combustion Test Device for Building Materials and Productsmain purpose
Zhongnuo DT-1 typeSingle unit combustion testing device for building materials and productsthistest deviceA specialized testing instrument used to test the reaction of building materials or products (excluding flooring materials) to fire in a single combustion test, in order to determine their physical properties. thistest deviceMeet the requirements of the national standard for testing conditions,Standard basisTest procedures (methods).
passtest deviceAfter testing, the combustion performance (grade) of the sample can be determined, including quantitative (qualitative) testing parameters: sample combustion heat release rate, whether flame lateral propagation occurs, calculation of total smoke production of the sample (smoke production performance), and whether there are droplets and particles produced during sample combustion.
thistest deviceEquipped with multiple testing functions, providing high-quality and cost-effective testing for quality inspection departments and enterprisestool
Zhongnuo GB/T 20284 Single Unit Combustion Test Device for Building Materials and Productsaccording to the standard
GB/T 20284-2006 Single unit combustion test for building materials or products
System testing project:
serial number |
test project |
1 |
Material (product) combustion heat release rate |
2 |
Total smoke production of materials (products) |
3 |
Material (product) flame lateral propagation (rate) |
4 |
Droplets and particles from materials (products) |
Technical Specifications
1. System temperature measurement range: 0-400 ℃; Measurement accuracy: ≤± 0.5 ℃;
2. System pressure difference measurement range: 0-100Pa(MAX); Measurement accuracy: ≤± 2Pa;
3. Smoke exhaust flow measurement range: 0.25m ³/s to 0.8 m ³/s (MAX); Measurement accuracy: ≤± 1.5%;
4Gas flow control accuracy: <647mg±10mg
5. Oxygen analysis (paramagnetic type) range: 16% to 21%, response time<12s,
6. The concentration range for measuring carbon dioxide (IR type) is 0% to 10%, with a linearity greater than 1% of the full scale,
8. Optical density measurement: measurement range 0% to 99.9%; Measurement accuracy: not exceeding ± 5% of the indicated value of the filter;
9. Measurement of relative humidity: measurement range: 20% to 80%, accuracy: ≤± 5%;
10. Fuel: Commercial propane gas, purity ≥ 95% (provided by the user);
11. Power supply: AC380V,6KW;
12. Equipment footprint dimensions (external dimensions of combustion chamber and exhaust duct): 6100mm × 5500mm × 4600mm (length × width × height);
13. External dimensions of combustion chamber: 3000mm×3000mm x 2500mm (length x width x height);
14. Can be accessed through a local area network
15. Equipped with ignition failure alarm detection system (optional)